FRP cable trays - Electric power & transmission & distribution

29 Apr.,2024

 

FRP cable trays - Electric power & transmission & distribution

INTELLIGENT WORK FORUMS
FOR ENGINEERING PROFESSIONALS

The company is the world’s best non metallic cable tray supplier. We are your one-stop shop for all needs. Our staff are highly-specialized and will help you find the product you need.

Contact US

FIRST NAME

*


LAST NAME

*


EMAIL

*


MESSAGE

*


ADDITIONAL DETAILS

Thanks. We have received your request and will respond promptly.

Log In

Come Join Us!

Are you an
Engineering professional?
Join Eng-Tips Forums!

  • Talk With Other Members
  • Be Notified Of Responses
    To Your Posts
  • Keyword Search
  • One-Click Access To Your
    Favorite Forums
  • Automated Signatures
    On Your Posts
  • Best Of All, It's Free!
Join Us!

*Eng-Tips's functionality depends on members receiving e-mail. By joining you are opting in to receive e-mail.

Posting Guidelines



Students Click Here

Promoting, selling, recruiting, coursework and thesis posting is forbidden.

Eng-Tips Posting Policies

Contact US

thread238-346891 Forum Search FAQs Links MVPs
  • Forum

  • Search

  • FAQs

  • Links

    For more plastic fermentation tanksinformation, please contact us. We will provide professional answers.

  • MVPs

FRP cable trays

FRP cable trays

cmelguet

(Electrical)

(OP)

16 Jun 13 11:27

Hi, I am involve in a project where we are running several 3 phase circuits of 33 kV using single phase conductors arranged in a trefoil formation. The cables are installed on a FRP cable ladder which is no good as a grounding conductor. The circuits lengths is around 1000 m, and all of the circuits goes from the main substation GIS switchgear to transformers 33/4.16 kV unitsubstations located around the plant.

Question: NEC requires to run a grounding conductor with every circuit. Normally the cable ladder is good enough for this. Since in this case i have an FRP cable ladder what are my alternatives?. Should I run an aditional grounding conductor for each circuit?. I understand the grounding grid is not good enough as a grounding conductor, even if all the grounding grids of the plant are joined together.

Regards,
Cristian

RE: FRP cable trays

7anoter4

(Electrical)

16 Jun 13 14:56

According to NEC 250.4 General Requirements for Grounding and Bonding. (B) Ungrounded Systems. (1) Grounding Electrical Equipment. you have to connect the equipment non-carrying current metallic parts to the local Grounding.
But according to (4) Path for Fault Current.:
"shall be installed in a manner that creates a low impedance
circuit from any point on the wiring system to
the electrical supply source to facilitate the operation of
overcurrent devices should a second ground fault from a
different phase occur on the wiring system. The earth shall
not be considered as an effective fault-current path."
you have to install a grounding conductor along 33 kV cable on the FRP cable tray.
The grounding conductor has to withstand the Line-to-Ground-to-Line short-circuit current.
I am not sure the metallic cable tray-even aluminum made-could withstand a medium voltage system short-circuit current. Aluminum cable tray is good only up to 2000 A.-a low voltage short-circuit, may be. See NEC Table 392.60(A)

RE: FRP cable trays

cmelguet

(Electrical)

(OP)

16 Jun 13 15:32

Thanks 7anoter4,

The 33 kV system is resistance grounded (600 A).
Another idea, the 33 kV cables installed in the cable ladder have a screen. Can i use the screen as a grounding conductor?. In this way i dont need to run a grounding cable along the FRP ladder.

Regards?

RE: FRP cable trays

davidbeach

(Electrical)

16 Jun 13 16:33

Generally the higher the voltage, the lower the fault current. 40kA is real easy to achieve at 480V, but rather rare in the 15kV range. Getting above 40kA at 115kV requires lots of sources.

RE: FRP cable trays

7anoter4

(Electrical)

17 Jun 13 10:07
"If the cable assembly is suitably rated for the ground fault current and is of the concentric neutral type, the shield conductors shall be permitted as the equipment grounding conductor."
NEC Table 250.122 for Rating or Setting of Automatic Overcurrent Device in Circuit Ahead of Equipment, Conduit, Not Exceeding 600 A recommends 1 awg [83.69 kcmil] copper conductor cross section.
See[for instance ] some concentric neutral cables:
http://www.prysmianusa.com/energy/product-families...

In my opinion, it is permitted according to NEC art.250.190 Grounding of Equipment.(C) Equipment Grounding Conductor. (2) Shielded Cables.:"If the cable assembly is suitably rated for the ground fault current and is of the concentric neutral type, the shield conductors shall be permitted as the equipment grounding conductor."NEC Table 250.122 for Rating or Setting of Automatic Overcurrent Device in Circuit Ahead of Equipment, Conduit, Not Exceeding 600 A recommends 1 awg [83.69 kcmil] copper conductor cross section.See[for instance ] some concentric neutral cables:

RE: FRP cable trays

7anoter4

(Electrical)

17 Jun 13 13:20

I have to mention since the shield is grounded at both ends the losses of circulating current induced in the shield requires cable derating. However, you can reduce this current by cross bonding and transposition.

Red Flag This Post

Please let us know here why this post is inappropriate. Reasons such as off-topic, duplicates, flames, illegal, vulgar, or students posting their homework.


Red Flag Submitted

Thank you for helping keep Eng-Tips Forums free from inappropriate posts.
The Eng-Tips staff will check this out and take appropriate action.

Reply To This Thread

Posting in the Eng-Tips forums is a member-only feature.

Click Here to join Eng-Tips and talk with other members! Already a Member? Login



News

For more information, please visit long life fiberglass storage tank.