How to wire a single-phase to 3-phase inverter?

06 May.,2024

 

FAQ: Can I connect a single-phase inverter to a three- ...

If you want to learn more, please visit our website single phase to three phase inverter.


This question has been coming up more frequently lately. I answered this many times at my previous company SMA America back in the early 2010s. Rapid shutdown wasn’t even a twinkle in the NEC patriarch’s eyes. Commercial rooftop solar started to take off and some people were leery about using microinverters and optimizers on such large systems. The largest central inverter at the time was the SMA 250kW Sunny Central. Huge for its time, revolutionary even, but by today’s standards it is a tick pulled off a gargantuan 2 MW central inverter, but still not the right inverter for some people.


Installers familiar with string inverters wanted to start stacking them up in these larger applications and the Code watchdogs and utility wienies started to ponder the implications. The National Electric Code and local utilities like PG&E in California had a lot to say about it, and it was good. Since most string inverters back then were single phase (sometimes referred to as split phase, meaning they had 2 hots, a neutral and ground), and most commercial buildings are three-phase (3 hots, a neutral and ground), people started asking questions. Oh, I should have started with a disclaimer, this post is going to get technical and very Codey.


Is it allowable for a single phase inverter (with L1 and L2 output) 2 pole breaker to connect to a 3-phase panel that has L1, L2, and L3 busbars?





This is a valid question considering commercial PV designs had 10 to 20 single phase inverters speced in. The obvious and easiest solution would be to install PV inverters in sets of three so that all phases would be accounted for, meaning no phase on the three phase panel would not be connected to at least one PV inverter output on any leg. Why the big fuss? Phase imbalances.


I am a big fan of citing my sources and did so in my book, The Battery Powered Home. The last section is devoted to my sources so that you know I am not pulling something out of my cloaca or parroting misinformation. However, that level of detail tends to make reading a little longer than normal.


The Code had guidelines for these imbalances to keep three phase motors from burning up if there was too large of a discrepancy between any of the three phases. Motors have manufacturing tolerances and if one leg of a three phase panel had more loads on it than the others, then the voltage would be lower and that phase of the motor would cause premature degradation. PG&E had a 6000W imbalance for this application and so the inspectors and AHJ adopted it for solar applications- as they were used to doing. Some people referenced phantom articles in the Code that stated 2% imbalance between any two lines but in another reference, it said 3%.


The imbalance stipulation did make it into the Code in Solar PV Systems section 690.63, then it was moved to 705.100, and now sits comfortably in 705.45 Unbalanced Interconnections. Before we get into the Code snoozefest, I want to explain the tech behind PV inverters and their grid interconnection.


PV inverters, regardless of how many are sending current to their respective breaker, do not know that there are two, three, or 20 other inverters on that panel. If you are confused about my use of the word “panel”, I am referring to the main service entrance of the installation, the breaker box, the Can, the AC distribution panel, the panel board, et. al. I am not referring to this:





That is a PV module, not a panel. And that’s all I am going to say about that in this post. If you call it a panel, you are wrong.


“But, people call them….”


No, you are wrong.


Multiple inverters feeding the same panel will not have a negative effect on the voltage unless:

1. There is an existing “significant” voltage imbalance.

2. The PV inverters are not installed in groups of three.


Notice the quotes. That leaves a lot of room for interpretation- which can be good or bad. Good for the installers who like these applications, but bad for the installers depending on the utility or AHJ interpretation of “significant”.


NEC 2020 705.45 Unbalanced Interconnections


(A) Single Phase. Single-phase power sources in interactive systems shall be connected to 3-phase power systems in order to limit unbalanced voltages at the point of interconnection to not more than 3 percent.

The company is the world’s best solar inverter companies supplier. We are your one-stop shop for all needs. Our staff are highly-specialized and will help you find the product you need.

Informational Note: For interactive power sources, unbalanced voltages can be minimized by the same methods that are used for single-phase loads on a 3-phase power system. See ANSI/C84.1-2016, Electric Power Systems and Equipment — Voltage Ratings (60 Hertz).


(B) Three Phase. Three-phase power sources in interactive systems shall have all phases automatically de-energized upon loss of, or unbalanced, voltage in one or more phases unless the interconnected system is designed so that significant unbalanced voltages will not result.


So, if you are installing single phase inverters on a three phase panel, it would be wise to see how much imbalance there is before you even get started slapping on these two-pole breakers. Let’s see how much imbalance there is from the utility lines with no loads on the panel. This is an easy exercise, but perhaps not so practical depending on the building. You will cut power to the panel and then measure the utility side voltage for all phases. Let’s use some not-so-realistic numbers for our calculations. FYI: Lower phase voltages mean more loads on that phase.


Phase A – B = 480V

Phase B – C = 475V

Phase A – C = 478V


I apologize in advance for the math. It is hard on the eyes, but an important part of this exercise.


Voltage Imbalance = 100 x Max Voltage Deviation from Average / Average Voltage


Average Voltage = 480 + 475 + 478 / 3 = 477.6

Max Voltage Deviation from Average = 477.6 – 475 = 2.6

Voltage Imbalance = (100 x 2.6) / 477.6 = .5%


This means the voltage from the utility is within 3% so now we need to perform this same exercise with the loads on. Turn on the three phase breaker and bust out that multimeter. We get different results with that main breaker on (voltages exaggerated for dramatic effect).


Phase A – B = 478V

Phase B – C = 475V

Phase A – C = 450V


Let’s plug in these new numbers:


Average Voltage = 478 + 475 + 450 / 3 = 467.6

Max Deviation from Average: 467.6 – 450 = 17.6

Voltage Imbalance = (100 x 17.6) / 467.6 = 3.7%


This panel exceeds the 3% rule, and if you think the utility will excuse that 0.7% I have a bridge in New York I’d like to sell you. But what are the implications of this voltage drop for our application?


First, if there are any three phase motors in this building they will suffer more wear and tear and will likely need to be serviced sooner than if the voltages were within the #5 tolerance.


Second, if you add single phase PV inverter breakers to this panel that are not divisible by three, it could make the imbalances worse. For example, installing three 40A two-pole breakers on this panel would not significantly contribute to the voltage imbalance. Probably. However, installing 10 or 11, probably would. Maybe. But here is the cool part:


The single phase inverters could actually help reduce the voltage imbalance on Phases C – A! So, in this case, I would put the two pole breakers for inverters #10 and #11 on Phase C – A and ensure the other inverter breakers were divided evenly amongst the other three phases. Done and done!




Conclusion:

Yes, Virginia, you can install single phase inverters on a three phase panel as long as you do not cause any significant imbalance and keep it under 3%.

Changing single phase to 3 phase

Thanks all, this was all very interesting.
So is my understanding correct, single phase L1 and L2 looked to be carried through and the converter actually generates a L3( image from stable means compared to straight capacitor use. (Brings up question below)
So

I've got a customer I've put power cords on some of his new woodworking equipment for him that the mfg install sheet indicated that the motors could be hooked up either by 1ph or 3ph and gave instructions of the connections and where to alter one of the internal connectors. He bought them pre set as a 1ph so my cord connection was simple red-red, black-black, green-green. No neutral connections.
So likely with these peices of equipment they are using a capacitor to "trick" the 3ph motor into spinning on 1ph. (Wow so devious, lol)

This brings up a question, this same customer has had some power issues when using his larger equipment. I'm going to assume they are the same type of motors as I just wired (3ph motor on 1ph supply). When any of these larger motor start there is a momentary flucuation in the power level of the system, but not consistent as to intensity or which phase (L1 or L2)on same motor. Could this be caused by the motors need for or ability to use 3 phase and the capacitor that shifts the phases? It does balance back out once motor starts. But the phenomenon lasts long enough to capture on a standard volt meter though. He wants to install led lighting in the shop so I wonder if this will become a more noticeable issue on the led vs his current fluorescents? I've seen issues with led and poor power quality.

Also, he is planning expanding his shop and with more equipment too. So would he be well served by getting one of these phase converters and using these tools on 3ph? Would that reduce the likelihood of needing to increase the system size all the way back to the utility? I know 3 ph uses a fraction the power as 1ph for the same hp motor (info from spec sheets not experience).

, this was all very interesting.So is my understanding correct, single phase L1 and L2 looked to be carried through and the converter actually generates a L3( image from @MTW ). And it seem from the one linked info that Larry gave it shifts the phase a little to put them at 120 deg from each other. It also stated that this way of getting 3 phase was the moremeans compared to straight capacitor use. (Brings up question below)So @Jraef this way of getting 3ph is actually using a 3phase motor inline to get the 3rd of a 3ph system? That is why I got wondering about it because that is what they look like, just a big motor, but it was getting 3ph output. It seems you could make one yourself out of a 3ph motor.I've got a customer I've put power cords on some of his new woodworking equipment for him that the mfg install sheet indicated that the motors could be hooked up either by 1ph or 3ph and gave instructions of the connections and where to alter one of the internal connectors. He bought them pre set as a 1ph so my cord connection was simple red-red, black-black, green-green. No neutral connections.So likely with these peices of equipment they are using a capacitor to "trick" the 3ph motor into spinning on 1ph. (Wow so devious, lol)This brings up a question, this same customer has had some power issues when using his larger equipment. I'm going to assume they are the same type of motors as I just wired (3ph motor on 1ph supply). When any of these larger motor start there is a momentary flucuation in the power level of the system, but not consistent as to intensity or which phase (L1 or L2)on same motor. Could this be caused by the motors need for or ability to use 3 phase and the capacitor that shifts the phases? It does balance back out once motor starts. But the phenomenon lasts long enough to capture on a standard volt meter though. He wants to install led lighting in the shop so I wonder if this will become a more noticeable issue on the led vs his current fluorescents? I've seen issues with led and poor power quality.Also, he is planning expanding his shop and with more equipment too. So would he be well served by getting one of these phase converters and using these tools on 3ph? Would that reduce the likelihood of needing to increase the system size all the way back to the utility? I know 3 ph uses a fraction the power as 1ph for the same hp motor (info from spec sheets not experience).

For more information, please visit senergy solar.